1. 适配器状态查询
发送: 01 04 00 00 00 01 31 CA
响应: 01 04 02 00 00 B9 30
2. 室内机连接状态
发送: 01 04 00 01 00 04 A0 09
响应: 01 04 08 00 00 00 00 00 00 00 00 24 0D
3. 室内机通信状态
发送: 01 04 00 05 00 04 E1 C8
响应: 01 04 08 00 00 00 00 00 00 00 00 24 0D
4. 室内机连接状态和室内机通信状态
发送: 01 04 00 01 00 08 A0 0C
响应: 01 04 10 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 55 2C
5. 尝试一种错误码
发送: 01 05 00 00 00 01 0C 0A
响应: 01 85 02 C3 51
6. 读取32001即室内机性能信息(室内机地址为1-00),三个寄存器
发送: 01 04 03 E8 00 03 30 7B
响应: 01 04 06 00 00 00 00 00 00 60 93
7. 读取32001即读取室内机性能信息(连续16个寄存器,不过已经超过了4台VRV室内机了,依旧可以正常通信,难道是室内机的不存在时,不算吗)
发送: 01 04 03 E8 00 0F 30 7E
响应: 01 04 1E 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 DA 3E
8. 读取室内机状态信息(室内机地址为1-00),6个寄存器
发送: 01 04 07 D0 00 06 70 85
响应: 01 04 0C 00 00 00 00 00 00 00 00 00 00 00 00 95 B7
9. 读取室内机状态嘻嘻(室内机地址从1-00到1-05),36个寄存器
发送: 01 04 07 D0 00 24 F0 9C
响应: 01 04 48 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 8B 0C
10. 预置单个寄存器42003即2002,设置温度为26.5度
发送: 01 06 07 D2 01 09 E9 11
响应: 01 06 07 D2 01 09 E9 11
11. 预置多个寄存器
发送: 01 10 07 D2 00 04 60 87 (数据格式明显是错误的)
响应: 01 90 03 0C 01
发送: 01 10 00 1D 00 04 08 01 23 04 56 07 89 0A BC D7 5F
响应: 01 90 02 CD C1